In stock
SKU
LC1D80BD
IQD 251,350
- [Ue] rated operational voltage : Power circuit <= 300 V DC 25...400 Hz
- Power circuit <= 690 V AC
About The Product
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 80 A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance.
Technical Data
- [Ue] rated operational voltage : Power circuit <= 300 V DC 25...400 Hz
- Power circuit <= 690 V AC
- [Ie] rated operational current : 125 A 140 °F (60 °C)) <= 440 V AC AC-1 power circuit
- 80 A 140 °F (60 °C)) <= 440 V AC AC-3 power circuit
- 80 A 140 °F (60 °C)) <= 440 V AC-3e power circuit
- [Uc] control circuit voltage : 24 V DC
- Motor power kW : 22 kW 220...230 V AC 50 Hz AC-3)
- 37 kW 380...400 V AC 50 Hz AC-3)
- 45 kW 415...440 V AC 50 Hz AC-3)
- 55 kW 500 V AC 50 Hz AC-3)
- 45 kW 660...690 V AC 50 Hz AC-3)
- 15 kW 400 V AC 50 Hz AC-4)
- 22 kW 220...230 V AC 50 Hz AC-3e)
- 37 kW 380...400 V AC 50 Hz AC-3e)
- 45 kW 415...440 V AC 50 Hz AC-3e)
- 55 kW 500 V AC 50 Hz AC-3e)
- 45 kW 660...690 V AC 50 Hz AC-3e)
- Motor power hp : 7.5 hp 120 V at AC 50/60 Hz for 1 phase
- 15 hp 230/240 V at AC 50/60 Hz for 1 phase
- 30 hp 200/208 V at AC 50/60 Hz for 3 phase
- 30 hp 230/240 V at AC 50/60 Hz for 3 phase
- 60 hp 460/480 V at AC 50/60 Hz for 3 phase
- 60 hp 575/600 V at AC 50/60 Hz for 3 phase
- Pole contact composition : 3 NO
- [Ith] conventional free air thermal current : 10 A 140 °F (60 °C) signaling circuit
- 125 A 140 °F (60 °C) power circuit
- Irms rated making capacity : 140 A AC signalling circuit IEC 60947-5-1
- 250 A DC signalling circuit IEC 60947-5-1
- 1100 A 440 V power circuit IEC 60947
- Rated breaking capacity : 1100 A 440 V power circuit IEC 60947
- Power dissipation per pole :5.1 W AC-3
- 12.5 W AC-1
- 5.1 W AC-3ePollution degree : 3
- [Uimp] rated impulse withstand voltage : 8 kV IEC 60947
- Mechanical durability : 4 Mcycles
- Electrical durability : 0.8 Mcycles 125 A AC-1 <= 440 V
- 1.5 Mcycles 80 A AC-3 <= 440 V
- 1.5 Mcycles 80 A AC-3e <= 440 V
- Control circuit voltage limits : 0.1...0.3 Uc -40…158 °F (-40…70 °C) drop-out DC
- 0.85...1.1 Uc -40…131 °F (-40…55 °C) operational DC
- 1...1.1 Uc 131…158 °F (55…70 °C) operational DC
- Inrush power in W : 22 W 68 °F (20 °C))
- Hold-in power consumption in W : 22 W 68 °F (20 °C)
- Operating time : 95...130 ms closing
- 20...35 ms opening
- Time constant : 75 ms
- Maximum operating rate : 3600 cyc/h 140 °F (60 °C)
- Permissible ambient air temperature around the device : -40…60 °C
- 60…70 °C with derating
- Fire resistance : 850 °C conforming to IEC 60695-2-1
- Height : 127 mm
- Width : 85 mm
- Depth : 186 mm
- Net weight : 2.59 kg
Write Your Own Review