In stock
SKU
LC1D80M7
IQD 126,350
- [Ue] rated operational voltage : Power circuit: <= 300 V DC 25...400 Hz
- Power circuit: <= 690 V AC
About The Product
TeSys D contactor, 3 poles (3NO), for motor control applications up to 80A/1000V AC-3/AC-3e (37kW@400V). control connection by screw clamp terminals, it procures high reliability and durability.
Technical Data
- [Ue] rated operational voltage : Power circuit: <= 300 V DC 25...400 Hz
- Power circuit: <= 690 V AC
- [Ie] rated operational current : 125 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
- 80 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
- 80 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
- [Uc] control circuit voltage : 220 V AC 50/60 Hz
- Motor power kW : 22 kW at 220...230 V AC 50/60 Hz (AC-3)
- 37 kW at 380...400 V AC 50/60 Hz (AC-3)
- 45 kW at 415...440 V AC 50/60 Hz (AC-3)
- 55 kW at 500 V AC 50/60 Hz (AC-3)
- 45 kW at 660...690 V AC 50/60 Hz (AC-3)
- 15 kW at 400 V AC 50/60 Hz (AC-4)
- 22 kW at 220...230 V AC 50/60 Hz (AC-3e)
- 37 kW at 380...400 V AC 50/60 Hz (AC-3e)
- 45 kW at 415...440 V AC 50/60 Hz (AC-3e)
- 55 kW at 500 V AC 50/60 Hz (AC-3e)
- 45 kW at 660...690 V AC 50/60 Hz (AC-3e)
- Motor power hp : 7.5 hp at 120 V AC 50/60 Hz for 1 phase motors
- 15 hp at 230/240 V AC 50/60 Hz for 1 phase motors
- 30 hp at 200/208 V AC 50/60 Hz for 3 phases motors
- 30 hp at 230/240 V AC 50/60 Hz for 3 phases motors
- 60 hp at 460/480 V AC 50/60 Hz for 3 phases motors
- 60 hp at 575/600 V AC 50/60 Hz for 3 phases motors
- Pole contact composition : 3 NO
- [Ith] conventional free air thermal current : 10 A (at 60 °C) for signaling circuit
- 125 A (at 60 °C) for power circuit
- Irms rated making capacity : 140 A AC for signalling circuit conforming to IEC 60947-5-1
- 250 A DC for signalling circuit conforming to IEC 60947-5-1
- 1100 A at 440 V for power circuit conforming to IEC 60947
- Rated breaking capacity : 1100 A at 440 V for power circuit conforming to IEC 60947
- Power dissipation per pole :5.1 W AC-3
- 12.5 W AC-1
- 5.1 W AC-3e
- Pollution degree : 3
- [Uimp] rated impulse withstand voltage : 8 kV conforming to IEC 60947
- Mechanical durability : 4 Mcycles
- Electrical durability : 0.8 Mcycles 125 A AC-1 at Ue <= 440 V
- 1.5 Mcycles 80 A AC-3 at Ue <= 440 V
- 1.5 Mcycles 80 A AC-3e at Ue <= 440 V
- Control circuit voltage limits : 0.85...1.1 Uc (-40…55 °C):operational AC 60 Hz
- 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz
- 0.8...1.1 Uc (-40…55 °C):operational AC 50 Hz
- 1...1.1 Uc (55…70 °C):operational AC 50/60 Hz
- Inrush power in VA : 26 VA 60 Hz cos phi 0.3 (at 20 °C)
- 26 VA 50 Hz cos phi 0.3 (at 20 °C)
- Hold-in power consumption in VA : 13 VA 60 Hz cos phi 0.3 (at 20 °C)
- 15 VA 50 Hz cos phi 0.3 (at 20 °C)
- Heat dissipation : 6…10 W at 50/60 Hz
- Operating time : 20...35 ms closing
- 6...20 ms opening
- Maximum operating rate : 3600 cyc/h 60 °C
- Permissible ambient air temperature around the device : -40…60 °C
- 60…70 °C with derating
- Fire resistance : 850 °C conforming to IEC 60695-2-1
- Height : 127 mm
- Width : 85 mm
- Depth : 130 mm
- Net weight : 1.59 kg
Write Your Own Review
Products from the same Schneider Electric