In stock
SKU
LC1D115BD
IQD 480,000
- [Ue] rated operational voltage : Power circuit <= 1000 V AC 25...400 Hz
- Power circuit <= 300 V DC
About The Product
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 115 A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance.
Technical Data
- [Ue] rated operational voltage : Power circuit <= 1000 V AC 25...400 Hz
- Power circuit <= 300 V DC
- [Ie] rated operational current : 200 A 140 °F (60 °C)) <= 440 V AC AC-1 power circuit
- 115 A 140 °F (60 °C)) <= 440 V AC AC-3 power circuit
- 115 A 140 °F (60 °C)) <= 440 V AC AC-3e power circuit
- [Uc] control circuit voltage : 24 V DC
- Motor power kW : 30 kW 220...230 V AC 50/60 Hz AC-3)
- 55 kW 380...400 V AC 50/60 Hz AC-3)
- 59 kW 415...440 V AC 50/60 Hz AC-3)
- 75 kW 500 V AC 50/60 Hz AC-3)
- 80 kW 660...690 V AC 50/60 Hz AC-3)
- 65 kW 1000 V AC 50/60 Hz AC-3)
- 18.5 kW 400 V AC 50/60 Hz AC-4)
- 30 kW 220...230 V AC 50/60 Hz AC-3e)
- 55 kW 380...400 V AC 50/60 Hz AC-3e)
- 59 kW 415...440 V AC 50/60 Hz AC-3e)
- 75 kW 500 V AC 50/60 Hz AC-3e)
- 80 kW 660...690 V AC 50/60 Hz AC-3e)
- 65 kW 1000 V AC 50/60 Hz AC-3e)
- Motor power hp : 30 hp 200/208 V at AC 50/60 Hz for 3 phase
- 40 hp 230/240 V at AC 50/60 Hz for 3 phase
- 75 hp 460/480 V at AC 50/60 Hz for 3 phase
- 100 hp 575/600 V at AC 50/60 Hz for 3 phase
- Pole contact composition : 3 NO
- [Ith] conventional free air thermal current : 200 A 140 °F (60 °C) power circuit
- Irms rated making capacity : 1260 A 440 V power circuit IEC 60947
- 140 A AC signaling circuit IEC 60947-5-1
- 250 A DC signaling circuit IEC 60947-5-1
- Rated breaking capacity : 1100 A 440 V power circuit IEC 60947
- Power dissipation per pole : 24 W AC-1
- 7.9 W AC-3
- 7.9 W AC-3e
- [Uimp] rated impulse withstand voltage : 8 kV IEC 60947
- Mechanical durability : 8 Mcycles
- Electrical durability : 0.8 Mcycles 200 A AC-1 <= 440 V
- 0.95 Mcycles 115 A AC-3 <= 440 V
- 0.95 Mcycles 115 A AC-3e <= 440 V
- Control circuit voltage limits : 0.75...1.2 Uc -40…131 °F (-40…55 °C) operational DC
- 0.15...0.4 Uc -40…158 °F (-40…70 °C) drop-out DC
- 1...1.2 Uc 131…158 °F (55…70 °C) operational DC
- Inrush power in W : 270…365 W 68 °F (20 °C))
- Hold-in power consumption in W :2.4…5.1 W 68 °F (20 °C)
- Operating time : 20...35 ms closing
- 40...75 ms opening
- Time constant : 25 ms
- Maximum operating rate : 1200 cyc/h 140 °F (60 °C)
- Permissible ambient air temperature around the device : -40…60 °C
- 60…70 °C with derating
- Fire resistance : 850 °C conforming to IEC 60695-2-1
- Height : 158 mm
- Width : 120 mm
- Depth : 136 mm
- Net weight : 2.5 kg