Description

About The Product


TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 95 A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance.

Technical Data


  • [Ue] rated operational voltage : Power circuit <= 690 V AC 25...400 Hz
  • [Ie] rated operational current : 95 A 140 °F (60 °C)) <= 440 V AC-3 power circuit
  • 125 A 140 °F (60 °C)) <= 690 V AC-1 power circuit
  • 95 A 140 °F (60 °C)) <= 440 V AC-3e power circuit
  • [Uc] control circuit voltage : 24 V DC
  • Motor power kW : 25 kW 220...230 V AC 50 Hz AC-3)
  • 45 kW 380...400 V AC 50 Hz AC-3)
  • 45 kW 415...440 V AC 50 Hz AC-3)
  • 55 kW 500 V AC 50 Hz AC-3)
  • 45 kW 660...690 V AC 50 Hz AC-3)
  • 15 kW 400 V AC 50 Hz AC-4)
  • 25 kW 220...230 V AC 50 Hz AC-3e)
  • 45 kW 380...400 V AC 50 Hz AC-3e)
  • 45 kW 415...440 V AC 50 Hz AC-3e)
  • 55 kW 500 V AC 50 Hz AC-3e)
  • 45 kW 660...690 V AC 50 Hz AC-3e)
  • Motor power hp : 7.5 hp 120 V at AC 60 Hz for 1 phase
  • 15 hp 230/240 V at AC 60 Hz for 1 phase
  • 30 hp 200/208 V at AC 60 Hz for 3 phase
  • 30 hp 230/240 V at AC 60 Hz for 3 phase
  • 60 hp 460/480 V at AC 60 Hz for 3 phase
  • 60 hp 575/600 V at AC 60 Hz for 3 phase
  • Pole contact composition : 3 NO
  • [Ith] conventional free air thermal current : 10 A 140 °F (60 °C) signaling circuit
  • 125 A 140 °F (60 °C) power circuit
  • Irms rated making capacity : 1100 A 440 V AC power circuit IEC 60947
  • 140 A AC signaling circuit IEC 60947-5-1
  • 250 A DC signaling circuit IEC 60947-5-1
  • Rated breaking capacity : 1100 A 440 V power circuit IEC 60947
  • Power dissipation per pole : 12.5 W AC-1
  • 7.2 W AC-3
  • 7.2 W AC-3e
  • [Uimp] rated impulse withstand voltage : 8 kV IEC 60947
  • Mechanical durability : 10 Mcycles
  • Electrical durability : 1.2 Mcycles 95 A AC-3
  • 1.3 Mcycles 125 A AC-1
  • 1.2 Mcycles 95 A AC-3e
  • Control circuit voltage limits : 0.1...0.3 Uc -40…158 °F (-40…70 °C) drop-out DC
  • 0.85...1.1 Uc -40…131 °F (-40…55 °C) operational DC
  • 1...1.1 Uc 131…158 °F (55…70 °C) operational DC
  • Inrush power in W : 22 W 68 °F (20 °C))
  • Hold-in power consumption in W : 22 W 68 °F (20 °C)
  • Operating time : 95...130 ms closing
  • 20...35 ms opening
  • Time constant : 75 ms
  • Maximum operating rate : 3600 cyc/h 140 °F (60 °C)
  • Permissible ambient air temperature around the device : -40…60 °C
  • 60…70 °C with derating
  • Fire resistance : 850 °C conforming to IEC 60695-2-1
  • Height : 127 mm
  • Width : 85 mm
  • Depth : 186 mm
  • Net weight : 2.61 kg
Product form

TeSys D contactor 3P AC3 95A 24V DC coil

[Ue] rated operational voltage : Power circuit [Ie] rated operational current : 95 A 140 °F (60 °C)) Read more

SKU: LC1D95BD

303,000 IQD

        [Ue] rated operational voltage : Power circuit [Ie] rated operational current : 95 A 140 °F (60 °C))

        Description

        About The Product


        TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 95 A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance.

        Technical Data


        • [Ue] rated operational voltage : Power circuit <= 690 V AC 25...400 Hz
        • [Ie] rated operational current : 95 A 140 °F (60 °C)) <= 440 V AC-3 power circuit
        • 125 A 140 °F (60 °C)) <= 690 V AC-1 power circuit
        • 95 A 140 °F (60 °C)) <= 440 V AC-3e power circuit
        • [Uc] control circuit voltage : 24 V DC
        • Motor power kW : 25 kW 220...230 V AC 50 Hz AC-3)
        • 45 kW 380...400 V AC 50 Hz AC-3)
        • 45 kW 415...440 V AC 50 Hz AC-3)
        • 55 kW 500 V AC 50 Hz AC-3)
        • 45 kW 660...690 V AC 50 Hz AC-3)
        • 15 kW 400 V AC 50 Hz AC-4)
        • 25 kW 220...230 V AC 50 Hz AC-3e)
        • 45 kW 380...400 V AC 50 Hz AC-3e)
        • 45 kW 415...440 V AC 50 Hz AC-3e)
        • 55 kW 500 V AC 50 Hz AC-3e)
        • 45 kW 660...690 V AC 50 Hz AC-3e)
        • Motor power hp : 7.5 hp 120 V at AC 60 Hz for 1 phase
        • 15 hp 230/240 V at AC 60 Hz for 1 phase
        • 30 hp 200/208 V at AC 60 Hz for 3 phase
        • 30 hp 230/240 V at AC 60 Hz for 3 phase
        • 60 hp 460/480 V at AC 60 Hz for 3 phase
        • 60 hp 575/600 V at AC 60 Hz for 3 phase
        • Pole contact composition : 3 NO
        • [Ith] conventional free air thermal current : 10 A 140 °F (60 °C) signaling circuit
        • 125 A 140 °F (60 °C) power circuit
        • Irms rated making capacity : 1100 A 440 V AC power circuit IEC 60947
        • 140 A AC signaling circuit IEC 60947-5-1
        • 250 A DC signaling circuit IEC 60947-5-1
        • Rated breaking capacity : 1100 A 440 V power circuit IEC 60947
        • Power dissipation per pole : 12.5 W AC-1
        • 7.2 W AC-3
        • 7.2 W AC-3e
        • [Uimp] rated impulse withstand voltage : 8 kV IEC 60947
        • Mechanical durability : 10 Mcycles
        • Electrical durability : 1.2 Mcycles 95 A AC-3
        • 1.3 Mcycles 125 A AC-1
        • 1.2 Mcycles 95 A AC-3e
        • Control circuit voltage limits : 0.1...0.3 Uc -40…158 °F (-40…70 °C) drop-out DC
        • 0.85...1.1 Uc -40…131 °F (-40…55 °C) operational DC
        • 1...1.1 Uc 131…158 °F (55…70 °C) operational DC
        • Inrush power in W : 22 W 68 °F (20 °C))
        • Hold-in power consumption in W : 22 W 68 °F (20 °C)
        • Operating time : 95...130 ms closing
        • 20...35 ms opening
        • Time constant : 75 ms
        • Maximum operating rate : 3600 cyc/h 140 °F (60 °C)
        • Permissible ambient air temperature around the device : -40…60 °C
        • 60…70 °C with derating
        • Fire resistance : 850 °C conforming to IEC 60695-2-1
        • Height : 127 mm
        • Width : 85 mm
        • Depth : 186 mm
        • Net weight : 2.61 kg
        • Multiple shipping options local and international

        • Original international brands

        • 100% secure payment methods

        • 24/7 support

        Viewed Products

        All Rights Reserved © TOOLMART 2025

            Login

            Forgot your password?

            Don't have an account yet?
            Create account