Professional 3-pole thermal magnetic circuit-breaker with 2A B-curve, 6kA/10kA breaking capacity, IP20 protection, and DIN rail mounting for reliable electrical installation protection.
The Legrand DX3 MCB 6000A is a professional-grade thermal magnetic circuit-breaker designed to protect and control wiring installations against overloads and short-circuits. This 3-pole device operates at 400V~ with a rated current of 2A and features a B-curve tripping characteristic, making it ideal for residential and small commercial panel applications. With a breaking capacity of 6kA/10kA and IP20 fingerproof design, this circuit-breaker provides reliable protection with maximum energy limitation (class 3 according to IEC 60898-1 standard).
This MCB features advanced safety and installation capabilities including DIN rail mounting with dual clamps for independent removal, compatibility with Legrand DX3 auxiliaries and RCD add-on modules, and support for multiple supply methods including copper cables, prong busbars, fork busbars, and Legrand HX3 plug busbars. The device includes a convenient label holder for circuit identification and clear ON/OFF indication printed on the handle with red and green backgrounds for easy status recognition. Built with halogen-free materials, this product complies with environmental and substance-restriction requirements.
The DX3 MCB is engineered for professional installation in compliance with electrical installation rules and is recommended to be installed by qualified electricians. It offers exceptional reliability with a rated insulation voltage of 500V, rated impulse withstand voltage of 4kV, and operates efficiently across 50-60Hz frequencies. The device is protected against solid bodies larger than 12.5mm and can be equipped with various Legrand accessories for enhanced functionality and customization.
Key Features
- Thermal magnetic protection against overloads and short-circuits with B-curve tripping characteristic
- 6kA/10kA breaking capacity with maximum energy limitation (class 3 per IEC 60898-1)
- IP20 fingerproof design protected against solid bodies larger than 12.5mm
- DIN rail mounting with dual clamps enabling independent removal without affecting busbar supply
- Compatible with Legrand DX3 auxiliaries, RCD add-on modules, and multiple supply methods
- Clear circuit identification with label holder and ON/OFF indication in red and green
- Halogen-free construction complying with environmental and substance-restriction requirements
- Rated insulation voltage 500V and impulse withstand voltage 4kV for enhanced safety
Technical Specifications
| Specification |
Value |
| Product Type | Thermal Magnetic Circuit Breaker (MCB) |
| Number of Poles | 3 poles (3P) |
| Rated Current | 2 Amperes (A) |
| Rated Voltage | 400V AC |
| Tripping Characteristic | B-curve (3In to 5In) |
| Breaking Capacity (Icn) | 6 kA at 400V per IEC 60898-1 |
| Breaking Capacity (Icu) | 10 kA at 400V per IEC 60947-2 |
| Breaking Capacity (Icu) | 25 kA at 230V per IEC 60947-2 |
| Rated Insulation Voltage (Ui) | 500V |
| Rated Impulse Withstand Voltage (Uimp) | 4 kV |
| Current Limiting Class | Class 3 |
| Degree of Protection | IP20 (fingerproof) |
| Degree of Impact Strength | IK02 |
| Pollution Degree | 2 |
| Frequency | 50-60 Hz |
| Width in Modular Spacings | 3 modules |
| Width | 53.1 mm |
| Height | 94.8 mm |
| Depth | 77.8 mm (built-in depth 44 mm) |
| Color | Grey (RAL 7035) |
| Connection Type | Screwed terminal |
| Connectable Conductor Cross Section (Multi-wired) | 1.5-25 mm² |
| Connectable Conductor Cross Section (Solid-core) | 1.5-35 mm² |
| Mounting Method | DIN rail |
| Supply Direction | By the top or bottom |
| Ambient Temperature Operating Range | -25°C to +70°C |
| Storage Temperature Range | -40°C to +70°C |
| Neutral Conductor Switching | No concurrent switching |
| Additional Equipment | Yes (compatible with DX3 auxiliaries and RCD add-on modules) |
| Halogen Free | Yes |
| Explosion-proof | No |
| Label Space | Yes (with label holder) |
| Flush-mounted Installation | Yes |
| Carbon Footprint (Manufacturing) | 3.151 kg CO₂ eq. |
| Reference Number | 407555 |
| EAN Code | 3245064075558 |
Order Legrand DX3 MCB 3P 2A Curve B Circuit Breaker | 407555 at wholesale prices for companies and factories in Iraq and Middle East, get the best deals on bulk purchases, contact us today.