| Product Name | MCB DX3 6000A 1 pole + neutral 40A curve B |
| Manufacturer | Legrand |
| Reference Number | 407479 |
| EAN Code | 3245064074797 |
| Breaking Capacity | 6000A according to IEC 60898-1 |
| Rated Current | 40A |
| Release Characteristic | B-curve (120A-200A tripping threshold, 3In-5In) |
| Rated Voltage | 230V AC |
| Rated Insulation Voltage | 250V |
| Rated Impulse Withstand Voltage | 4kV |
| Short-Circuit Breaking Capacity (Icn) | 6kA at 230V per EN 60898 |
| Short-Circuit Breaking Capacity (Icu) | 10kA at 230V per IEC 60947-2 |
| Number of Poles | 2 (1 protected pole + neutral) |
| Current Limiting Class | 3 |
| Degree of Protection | IP20 (fingerproof) |
| Impact Strength | IK02 |
| Frequency | 50-60 Hz |
| Built-in Depth | 44mm |
| Width | 17.8mm |
| Height | 94.8mm |
| Depth | 77.6mm |
| Width in Modular Spacings | 1 |
| Color | Grey (RAL 7035) |
| Connectable Conductor Cross Section (Multi-wired) | 0.75-10mm² |
| Connectable Conductor Cross Section (Solid-core) | 0.75-16mm² |
| Connection Type | Screwed terminal, Busbar and cable |
| Electric Supply Direction | Top or bottom |
| Ambient Temperature (Operating) | -25°C to 70°C |
| Storage Temperature | -40°C to 70°C |
| Nominal Voltage Range | 210-250V |
| Pollution Degree | 2 |
| Mounting Method | DIN rail |
| Flush-mounted Installation | Yes |
| Concurrently Switching Neutral | Yes |
| Additional Equipment Possible | Yes |
| Terminal Marking Indication | Yes |
| Label Space/Information Surface | Yes |
| Halogen Free | Yes |
| Explosion-proof | No |
| Carbon Footprint (Manufacturing) | 0.760 kg CO2 eq. |
| Compliance Standards | IEC 60898-1, IEC 60947-2, IEC/EN 60529, RoHS, REACH |