| Product Name | MCB DX3 6000A 2 pole 6A curve C |
| Reference Number | 407796 |
| EAN Code | 3245064077965 |
| Breaking Capacity | 6kA according to IEC 60898-1 |
| Number of Poles | 2 poles (2 protected poles) |
| Rated Current | 6 Amperes |
| Release Characteristic | C curve (5 In to 10 In) |
| Rated Voltage | 400V AC |
| Rated Insulation Voltage | 500V |
| Impulse Withstand Voltage | 4kV |
| Short-Circuit Breaking Capacity (Icn) | 6kA at 400V per EN 60898 |
| Short-Circuit Breaking Capacity (Icu) | 25kA at 230V and 10kA at 400V per IEC 60947-2 |
| Frequency Range | 50-60 Hz |
| Current Limiting Class | 3 (Maximum energy limitation) |
| Degree of Protection | IP20 (Fingerproof) |
| Impact Strength Rating | IK02 |
| Built-in Depth | 44mm |
| Width | 35.4mm (2 modular spacings) |
| Height | 94.8mm |
| Total Depth | 77.8mm |
| Connectable Conductor Cross-Section (Solid-Core) | 1.5-35mm² |
| Connectable Conductor Cross-Section (Multi-Wired) | 1.5-25mm² |
| Connection Type | Screwed Terminal |
| Mounting Method | DIN Rail |
| Supply Direction | Top or Bottom |
| Colour | Grey (RAL 7035) |
| Operating Temperature Range | -25°C to +70°C |
| Storage Temperature Range | -40°C to +70°C |
| Pollution Degree | 2 |
| Halogen Free | Yes |
| Flush-Mounted Installation | Yes |
| Neutral Conductor Switching | No |
| Additional Equipment Compatible | Yes - Legrand DX3 auxiliaries, RCD modules, accessories |
| Carbon Footprint (Manufacturing) | 1.653 kg CO₂ eq. |
| Standards Compliance | IEC 60898-1, IEC 60947-2, IEC/EN 60529, RoHS, REACH |