Thermal magnetic circuit-breaker with 2P configuration, 2A rated current, C curve characteristic, and 16kA breaking capacity at 230V. Offers IP20 fingerproof protection, DIN rail mounting, and complies with IEC 60898-1 standard for household installations.
The Legrand DX3 MCB 2P 2A C Curve is a thermal magnetic circuit-breaker designed to protect wiring installations against overloads and short-circuits. This device features a 2-pole configuration with a 2A rated current and C curve release characteristic, providing reliable protection for residential and small commercial applications. With a breaking capacity of 16kA at 230V and 10kA at 400V, it meets the IEC 60898-1 standard for household installations. The MCB offers IP20 fingerproof safety rating, protecting against solid bodies larger than 12.5mm, and features DIN rail mounting for easy installation. Its compact design with 35.4mm width allows for efficient space utilization in distribution panels.
This circuit-breaker can be supplied through multiple connection methods including copper cable, prong busbar, fork busbar, or Legrand HX3 plug busbar. The device includes a label holder for clear circuit identification and On/Off indication printed on the handle with red and green backgrounds for easy status recognition. It is equipped with two DIN rail clamps (top and bottom), allowing independent removal while the prong busbar remains in place. The C curve characteristic provides a tripping threshold between 5In and 10In, making it suitable for general purpose circuits with moderate inrush currents.
The DX3 MCB is halogen-free and designed with environmental consciousness in mind, complying with substance-restriction requirements. It can be equipped with Legrand DX3 auxiliaries, RCD add-on modules, and various accessories for enhanced functionality. The device operates reliably in ambient temperatures ranging from -25°C to 70°C and features current limiting class 3 for maximum energy limitation. With a connectable conductor cross-section ranging from 1.5-35mm² for solid-core cables and 1.5-25mm² for multi-wired cables, it accommodates various installation requirements.
Key Features
- Breaking capacity of 16kA at 230V and 10kA at 400V according to IEC 60898-1 standard
- IP20 fingerproof protection against solid bodies larger than 12.5mm
- C curve release characteristic with tripping threshold between 5In and 10In
- DIN rail mounting with independent top and bottom clamps for easy removal
- Compatible with Legrand DX3 auxiliaries, RCD add-on modules, and accessories
- Current limiting class 3 for maximum energy limitation
- Label holder for clear circuit identification with On/Off indication
- Halogen-free and environmentally conscious design
- Compact 35.4mm width for efficient space utilization
- Multiple connection options: copper cable, prong busbar, fork busbar, or HX3 plug busbar
Technical Specifications
| Specification |
Value |
| Product Reference | 409196 |
| EAN Code | 3245064091961 |
| Brand | Legrand |
| Series | DX³ |
| Type | Thermal Magnetic Circuit-Breaker (MCB) |
| Number of Poles | 2 |
| Rated Current | 2 A |
| Release Characteristic | C Curve |
| Rated Voltage | 400 V AC |
| Rated Insulation Voltage | 500 V |
| Rated Impulse Withstand Voltage | 4 kV |
| Breaking Capacity at 230V | 16 kA (Icn) |
| Breaking Capacity at 400V | 10 kA (Icn) |
| Ultimate Breaking Capacity at 230V | 32 kA (Icu) |
| Ultimate Breaking Capacity at 400V | 16 kA (Icu) |
| Current Limiting Class | 3 |
| Degree of Protection | IP20 |
| Frequency | 50-60 Hz |
| Width in Modular Spacings | 2 |
| Width | 35.4 mm |
| Height | 94.8 mm |
| Depth | 77.8 mm |
| Built-in Depth | 44 mm |
| Degree of Impact Strength | IK02 |
| Connectable Conductor Cross Section (Solid-core) | 1.5-35 mm² |
| Connectable Conductor Cross Section (Multi-wired) | 1.5-25 mm² |
| Connection Type | Screwed Terminal |
| Electric Supplying Direction | By the top or bottom |
| Mounting Method | DIN Rail |
| Flush-mounted Installation | Yes |
| Concurrently Switching Neutral Conductor | No |
| Pollution Degree | 2 |
| Additional Equipment Possible | Yes |
| Operating Temperature Range | -25 to 70°C |
| Storage Temperature Range | -40 to 70°C |
| Colour | Grey |
| RAL Number | 7035 |
| Halogen Free | Yes |
| Label Space/Information Surface | Yes |
| Explosion-proof | No |
| Carbon Footprint (Manufacturing Phase) | 1.958 kg CO₂ eq. |
| Compliance Standards | IEC 60898-1, IEC 60947-2, IEC/EN 60529 |
| Tripping Threshold | Between 5In and 10In |
| Number of Protected Poles | 2 |
Order Legrand DX3 MCB 2P 2A C Curve Circuit Breaker | 409196 at wholesale prices for companies and factories in Iraq and Middle East, get the best deals on bulk purchases, contact us today.