Shop Legrand DX3 MCB 2P 16A C Curve 6000A Circuit Breaker | 407800 In Iraq Best Prices
Professional-grade 2-pole thermal magnetic circuit-breaker with 16A rating, 6000A breaking capacity, and C-curve protection for residential and commercial electrical installations
The Legrand DX3 MCB 6000A is a high-performance thermal magnetic circuit-breaker specifically designed to protect wiring installations against overloads and short-circuits. With a rated current of 16A and C-curve tripping characteristic, this 2-pole device delivers exceptional reliability for residential and small commercial applications. Rated at 230/400V AC with a breaking capacity of 6000A according to IEC 60898-1 standard, it features energy limitation class 3 and IP20 fingerproof protection. The device can be supplied via copper cable, prong busbar, fork busbar, or Legrand HX3 plug busbar, offering flexible installation options. Its compact 44mm built-in depth and DIN rail mounting system with independent clamps allow convenient installation and removal without affecting the main busbar supply.
This circuit-breaker is equipped with advanced safety features including a tripping threshold for short-circuits between 80A and 160A (C curve between 5 In and 10 In), providing optimal protection for household and light commercial installations. The device is compatible with Legrand DX3 auxiliaries, RCD add-on modules, and various accessories, making it highly versatile for different installation scenarios. It features a label holder for clear circuit identification and ON/OFF indication printed on the handle with red and green backgrounds for easy status identification. The product complies with substance-restriction requirements and has been designed in an environmentally conscious process, meeting all modern safety and environmental standards.
Installation should be performed by qualified electricians in compliance with local installation rules. The device features screwed terminals compatible with multi-wired conductors (1.5-25mm²) and solid-core conductors (1.5-35mm²), ensuring compatibility with various cable types. Operating temperature range is -25 to 70°C, with storage temperature capability from -40 to 70°C, making it suitable for diverse environmental conditions. The halogen-free design and comprehensive certification documentation ensure this product meets international safety standards and environmental regulations.
Key Features
- Breaking capacity of 6000A according to IEC 60898-1 standard for household and light commercial installations
- C-curve tripping characteristic with short-circuit threshold between 80A and 160A for optimal protection
- IP20 fingerproof protection against solid bodies larger than 12.5mm per IEC/EN 60529
- Energy limitation class 3 providing maximum level of let-through energy reduction
- Compatible with Legrand DX3 auxiliaries, RCD add-on modules, and comprehensive accessories
- Independent DIN rail clamps for convenient installation and removal without affecting main busbar
- Label holder with ON/OFF indication for clear circuit identification and status visibility
- Flexible supply options: copper cable, prong busbar, fork busbar, or Legrand HX3 plug busbar
- Halogen-free design meeting environmental and substance-restriction requirements
- Wide operating temperature range from -25°C to +70°C for diverse environmental conditions
Technical Specifications
| Specification |
Value |
| Product Type | Thermal Magnetic Circuit-Breaker (MCB) |
| Number of Poles | 2 poles (2P) |
| Rated Current | 16 Amperes (A) |
| Release Characteristic | C curve |
| Rated Voltage | 400V AC (230/400V~) |
| Rated Insulation Voltage | 500V |
| Rated Impulse Withstand Voltage | 4 kV |
| Breaking Capacity (Icn) | 6000A at 400V according to EN 60898 |
| Breaking Capacity (Icu) at 230V | 25 kA according to IEC 60947-2 |
| Breaking Capacity (Icu) at 400V | 10 kA according to IEC 60947-2 |
| Current Limiting Class | Class 3 |
| Degree of Protection | IP20 (fingerproof) |
| Built-in Depth | 44 mm |
| Width (Modular Spacings) | 2 modules |
| Width Dimension | 35.4 mm |
| Height Dimension | 94.8 mm |
| Depth Dimension | 77.8 mm |
| Degree of Impact Strength | IK02 |
| Operating Temperature Range | -25°C to +70°C |
| Storage Temperature Range | -40°C to +70°C |
| Frequency | 50-60 Hz |
| Connectable Conductor (Multi-wired) | 1.5-25 mm² |
| Connectable Conductor (Solid-core) | 1.5-35 mm² |
| Connection Type | Screwed terminal |
| Mounting Method | DIN rail |
| Pollution Degree | 2 |
| Colour | Grey (RAL 7035) |
| Halogen Free | Yes |
| Flush-mounted Installation | Yes |
| Concurrently Switching Neutral | No |
| Explosion-proof | No |
| Additional Equipment Possible | Yes |
| Tripping Threshold (Short-circuit) | 80A to 160A (C curve: 5 In to 10 In) |
| Supply Options | Copper cable, prong busbar (top/bottom), fork busbar (bottom), Legrand HX3 plug busbar (top) |
| Compatible Accessories | Legrand DX3 auxiliaries, RCD add-on modules, DX3 accessories |
| Reference Number | 407800 |
| EAN Code | 3245064078009 |
| Carbon Footprint (Manufacturing) | 1.631 kg CO2 eq. |
Order Legrand DX3 MCB 2P 16A C Curve 6000A Circuit Breaker | 407800 at wholesale prices for companies and factories in Iraq and Middle East, get the best deals on bulk purchases, contact us today.