Legrand DX3 modular 2-pole thermal-magnetic circuit breaker with 80A D-curve rating, 10kA/16kA breaking capacity, IP20 finger-safe design, and DIN rail mounting for residential and small commercial electrical protection
The Legrand DX3 MCB 2 Pole 80A Curve D Circuit Breaker is a modular thermal-magnetic circuit breaker designed for comprehensive control, protection, and isolation of electrical circuits in residential and small commercial installations. This device features a D-curve release characteristic with 10kA breaking capacity according to IEC 60898-1 standard and 16kA breaking capacity according to IEC 60947-2, making it suitable for applications requiring moderate inrush current tolerance. The circuit breaker is equipped with IP20 finger-safe protection, red/green mechanical indicator for status display, and a label holder for convenient circuit identification.
The DX3 80A 2-pole breaker is constructed with a built-in depth of 47mm and operates at rated voltage of 400V with insulation voltage of 500V. It features screwed terminal connections compatible with multi-wired conductors of 6-50mm² and solid-core conductors of 6-70mm². The device can be supplied from the top or bottom and is mountable on DIN rail systems. With a tripping threshold between 800A and 1120A, this D-curve breaker provides reliable short-circuit protection while accommodating moderate load variations typical in residential and small commercial applications.
Designed with environmental consciousness, this halogen-free device complies with substance-restriction requirements and RoHS directives. The DX3 series is compatible with Legrand auxiliaries, RCD add-on modules, and various accessories, allowing for flexible system configuration. Operating across a frequency range of 50-60Hz and ambient temperatures from -25°C to 70°C, this circuit breaker delivers consistent performance and protection throughout its operational life. Installation should be performed by qualified electricians in compliance with local electrical codes and installation rules.
Key Features
- D-curve release characteristic with 10kA breaking capacity (IEC 60898-1) and 16kA breaking capacity (IEC 60947-2) for reliable short-circuit protection
- IP20 finger-safe protection with 35.4mm width for compact modular installation on DIN rail systems
- Red/green mechanical indicator and label holder for clear circuit identification and status display
- Compatible with Legrand DX3 auxiliaries, RCD add-on modules, and accessories for flexible system configuration
- Halogen-free design complying with RoHS and substance-restriction requirements for environmental sustainability
- Thermal-magnetic tripping with 800A-1120A threshold for moderate inrush current applications
- Screwed terminal connections supporting 6-70mm² solid-core and 6-50mm² multi-wired conductors
- Top or bottom supply capability with 400V rated voltage and 500V insulation voltage
- Operating temperature range -25°C to 70°C with 50-60Hz frequency compatibility
- IK02 impact resistance rating suitable for residential and small commercial environments
Technical Specifications
| Specification |
Value |
| Product Type | Modular Thermal-Magnetic Circuit Breaker |
| Number of Poles | 2 poles |
| Rated Current | 80 Amperes |
| Release Characteristic | D-curve |
| Breaking Capacity IEC 60898-1 | 10,000 Amperes (10kA) |
| Breaking Capacity IEC 60947-2 at 400V | 16,000 Amperes (16kA) |
| Rated Voltage | 400 Volts AC |
| Insulation Voltage | 500 Volts |
| Impulse Withstand Voltage | 4 kV |
| Frequency Range | 50-60 Hz |
| Tripping Threshold | 800A to 1120A (D-curve between 10In and 14In) |
| Degree of Protection | IP20 (finger-safe) |
| Impact Resistance | IK02 |
| Built-in Depth | 47 millimeters |
| Width | 35.4 millimeters |
| Height | 94.8 millimeters |
| Total Depth | 77.8 millimeters |
| Modular Width | 3 modular spacings |
| Connection Type | Screwed Terminal |
| Solid-Core Conductor Range | 6-70 square millimeters |
| Multi-Wired Conductor Range | 6-50 square millimeters |
| Supply Direction | Top or bottom |
| Mounting Method | DIN rail |
| Operating Temperature Range | -25°C to +70°C |
| Storage Temperature Range | -40°C to +70°C |
| Pollution Degree | 2 |
| Color | Grey (RAL 7035) |
| Halogen Free | Yes |
| Flush-Mounted Installation | Yes |
| Neutral Conductor Switching | No |
| Additional Equipment Possible | Yes - Compatible with DX3 auxiliaries and RCD modules |
| Label Space | Yes |
| Carbon Footprint Manufacturing | 3.112 kg CO2 equivalent |
| Reference Number | 409458 |
| EAN Code | 3245064094580 |
| Standards Compliance | IEC 60898-1, IEC 60947-2, IEC/EN 60529, RoHS, REACH |