Shop Legrand DX3 MCB 2 Pole 32A Curve D 6000A Circuit Breaker | 408034 In Iraq Best Prices
Thermal magnetic 2-pole circuit breaker with 32A rating, D-curve characteristic, and 6000A breaking capacity for reliable overcurrent protection in residential and commercial installations. Features DIN rail mounting, accepts DX3 auxiliaries, and provides both control and isolation functions.
The Legrand DX3 MCB 2 Pole 32A Curve D is a thermal magnetic circuit-breaker designed to protect wiring installations against overloads and short-circuits with a breaking capacity of 6000A according to IEC 60898-1 standard. This high-performance modular circuit breaker features a D-curve tripping characteristic with a short-circuit threshold between 320A and 448A (10 In to 14 In), making it ideal for residential and small commercial panel applications. The device can be supplied via copper cable, prong busbar, fork busbar, or Legrand HX3 plug busbar connections, offering flexible installation options.
Beyond protection, this MCB provides control and isolation functions for the installation while accepting DX3 auxiliaries and RCD add-on modules for enhanced functionality. The device is IP20 rated (fingerproof against solid bodies larger than 12.5mm) and complies with IEC/EN 60529 standards for safety. With its compact design measuring 35.4mm width and 44mm built-in depth, it fits efficiently into standard DIN rail installations with two independent clamps for reliable mounting. The integrated label holder with ON/OFF indication printed on red and green backgrounds ensures clear circuit identification and status visibility.
This environmentally conscious product is halogen-free and manufactured according to substance-restriction requirements. It supports both solid-core conductors (1.5-35mm²) and multi-wired conductors (1.5-25mm²), with an operating temperature range of -25°C to 70°C. The Legrand DX3 MCB combines technical excellence with user-friendly design, making it an essential component for modern electrical installations requiring reliable overcurrent protection and circuit management.
Key Features
- 6000A breaking capacity according to IEC 60898-1 standard for household installations
- D-curve tripping characteristic with short-circuit threshold between 320A-448A (10 In to 14 In)
- Multiple supply options: copper cable, prong busbar, fork busbar, or Legrand HX3 plug busbar
- Accepts DX3 auxiliaries, RCD add-on modules, and compatible accessories for enhanced functionality
- IP20 rated protection (fingerproof against solid bodies larger than 12.5mm) per IEC/EN 60529
- Integrated label holder with ON/OFF status indication on red and green backgrounds
- Independent DIN rail clamps for secure mounting and easy removal
- Supports solid-core (1.5-35mm²) and multi-wired (1.5-25mm²) conductor connections
- Halogen-free and environmentally conscious manufacturing process
- Compact modular design: 35.4mm width, 44mm built-in depth, suitable for standard panels
Technical Specifications
| Specification |
Value |
| Product Type | Thermal Magnetic Circuit Breaker (MCB) |
| Number of Poles | 2 poles (2P) |
| Rated Current | 32 A |
| Tripping Curve | D-curve (10 In to 14 In) |
| Breaking Capacity | 6000A (Icn) at 400V according to EN 60898-1 |
| Rated Voltage | 400V AC |
| Rated Insulation Voltage | 500V |
| Impulse Withstand Voltage | 4 kV |
| Short-Circuit Breaking Capacity (Icu) | 25 kA at 230V; 10 kA at 400V (IEC 60947-2) |
| Frequency | 50-60 Hz |
| Degree of Protection | IP20 (fingerproof) |
| Impact Strength | IK02 |
| Operating Temperature Range | -25°C to +70°C |
| Storage Temperature Range | -40°C to +70°C |
| Pollution Degree | 2 |
| Conductor Cross Section (Solid-Core) | 1.5 to 35 mm² |
| Conductor Cross Section (Multi-Wired) | 1.5 to 25 mm² |
| Connection Type | Screwed Terminal |
| Supply Direction | By top or bottom |
| Width | 35.4 mm (2 modular spacings) |
| Height | 94.8 mm |
| Depth | 77.8 mm (built-in depth: 44 mm) |
| Mounting Method | DIN rail (35 mm standard) |
| Color | Grey (RAL 7035) |
| Material | Halogen-free |
| Neutral Conductor Switching | No |
| Additional Equipment Possible | Yes (DX3 auxiliaries, RCD modules) |
| Flush-Mounted Installation | Yes |
| Reference Number | 408034 |
| EAN Code | 3245064080347 |
| Carbon Footprint (Manufacturing) | 1.803 kg CO₂ eq. |
Order Legrand DX3 MCB 2 Pole 32A Curve D 6000A Circuit Breaker | 408034 at wholesale prices for companies and factories in Iraq and Middle East, get the best deals on bulk purchases, contact us today.