| Product Type | Thermal Magnetic Circuit Breaker (MCB) |
| Rated Current | 32A |
| Release Characteristic | C Curve |
| Number of Poles | 1 Pole + Neutral (2 total poles) |
| Rated Voltage | 230V AC |
| Breaking Capacity (Icn) | 6000A at 230V according to IEC 60898-1 |
| Breaking Capacity (Icu) | 10000A at 230V according to IEC 60947-2 |
| Rated Insulation Voltage | 250V |
| Impulse Withstand Voltage | 4kV |
| Tripping Threshold (Short Circuit) | 160A to 320A (C curve between 5In and 10In) |
| Current Limiting Class | 3 |
| Protection Degree | IP20 (Fingerproof) |
| Impact Strength Degree | IK02 |
| Mounting Method | DIN Rail with 2 independent clamps |
| Width | 17.8mm (1 modular spacing) |
| Height | 94.8mm |
| Depth | 77.6mm (Built-in depth 44mm) |
| Connectable Conductor Cross Section (Multi-wired) | 0.75-10mm² |
| Connectable Conductor Cross Section (Solid-core) | 0.75-16mm² |
| Connection Type | Screwed terminal, Busbar and cable |
| Electric Supplying Direction | By the top or bottom |
| Ambient Temperature Operating Range | -25°C to 70°C |
| Storage Temperature Range | -40°C to 70°C |
| Nominal Voltage Range | 210-250V |
| Frequency | 50-60Hz |
| Voltage Type | AC |
| Pollution Degree | 2 |
| Color | Grey (RAL 7035) |
| Halogen Free | Yes |
| Concurrent Switching Neutral Conductor | Yes |
| Terminal Marking Indication | Yes |
| Label Space/Information Surface | Yes |
| Additional Equipment Possible | Yes (Legrand DX3 auxiliaries and accessories) |
| Flush-mounted Installation | Yes |
| Explosion-proof | No |
| Carbon Footprint (Manufacturing Phase) | 0.755 kg CO₂ eq. |
| Reference Number | 407745 |
| EAN Code | 3245064077453 |