| Product Type | Thermal Magnetic Circuit Breaker (MCB) |
| Rated Current | 1 A |
| Rated Voltage | 230V AC |
| Rated Insulation Voltage (Ui) | 250V |
| Rated Impulse Withstand Voltage (Uimp) | 4 kV |
| Breaking Capacity (Icn) at 230V | 6 kA according to EN 60898-1 |
| Ultimate Breaking Capacity (Icu) at 230V | 10 kA according to IEC 60947-2 |
| Trip Characteristic | C Curve (5In to 10In) |
| Number of Poles (Total) | 2 poles (1 pole + neutral) |
| Number of Protected Poles | 1 pole |
| Current Limiting Class | Class 3 |
| Degree of Protection (IP) | IP20 (Fingerproof) |
| Degree of Impact Strength (IK) | IK02 |
| Mounting Method | DIN rail (35mm) |
| Width | 17.8 mm (1 modular spacing) |
| Height | 94.8 mm |
| Depth | 77.6 mm (Built-in depth: 44mm) |
| Connectable Conductor Cross Section (Multi-wired) | 0.75 - 10 mm² |
| Connectable Conductor Cross Section (Solid-core) | 0.75 - 16 mm² |
| Connection Type | Screwed terminal, Busbar and cable (top or bottom supply) |
| Frequency Range | 50 - 60 Hz |
| Voltage Type | AC |
| Nominal Voltage Range | 210 - 250V |
| Ambient Temperature (Operating) | -25°C to +70°C |
| Storage Temperature | -40°C to +70°C |
| Pollution Degree | 2 |
| Concurrently Switching Neutral | Yes |
| Flush-mounted Installation | Yes |
| Additional Equipment Possible | Yes (Legrand DX3 auxiliaries and accessories) |
| Colour | Grey (RAL 7035) |
| Halogen Free | Yes |
| Terminal Marking | Yes |
| Label Space | Yes (Label holder included) |
| Explosion-proof | No |
| Reference Number | 407734 |
| EAN Code | 3245064077347 |
| Carbon Footprint (Manufacturing) | 0.719 kg CO2 eq. |