Shop Legrand DX3 MCB 1P 6A Curve D Circuit Breaker 6kA | 407967 In Iraq Best Prices
Single-pole thermal magnetic circuit breaker with 6A rating, D-curve tripping, and 6kA breaking capacity for residential and small commercial wiring protection
The Legrand DX3 MCB 6000A is a thermal magnetic circuit-breaker designed to protect wiring installations against overloads and short-circuits. This single-pole device features a 6kA breaking capacity at 230V and D-curve tripping characteristics between 60A to 84A, making it ideal for household and small commercial installations. The breaker is also used to control and isolate the installation effectively. With its IP20 protection rating and fingerproof design (protected against solid bodies larger than 12.5mm), it ensures safe operation in various environments. The device can be supplied by copper cable, prong busbar, fork busbar, or Legrand HX3 plug busbar, providing flexible installation options. It complies with IEC 60898-1 standard for household installations and features environmentally conscious design principles.
This MCB offers comprehensive installation flexibility with two DIN rail clamps (one top side and one bottom side) allowing independent removal while the prong busbar remains in place. The device includes a label holder for clear circuit identification and features ON/OFF indication printed on the handle with red and green backgrounds for easy status identification. It can be equipped with Legrand DX3 auxiliaries, RCD add-on modules, and various accessories to meet specific application requirements. The rated insulation voltage is 500V with a rated impulse withstand voltage of 4kV, ensuring reliable performance under demanding conditions.
The technical specifications include a built-in depth of 44mm, width of 17.8mm (1 modular spacing), and height of 94.8mm, making it compact and suitable for standard DIN rail installations. It operates at a rated voltage of 230V AC with frequency range of 50-60Hz and maintains performance across ambient temperatures from -25°C to 70°C. The device features screwed terminal connections capable of handling multi-wired conductors from 1.5-25mm² and solid-core conductors from 1.5-35mm². With a Pollution Degree 2 rating and IK02 impact strength, it provides robust protection in standard industrial and domestic environments.
Key Features
- 6kA breaking capacity at 230V according to IEC 60898-1 standard for household installations
- D-curve tripping characteristic between 60A and 84A for reliable overload and short-circuit protection
- IP20 protection rating with fingerproof design protecting against solid bodies larger than 12.5mm
- Flexible supply options including copper cable, prong busbar, fork busbar, or Legrand HX3 plug busbar
- Compatible with Legrand DX3 auxiliaries, RCD add-on modules and comprehensive accessories
- Dual DIN rail clamps allowing independent removal while busbar remains in place
- Clear circuit identification with label holder and ON/OFF indication on handle
- Environmentally conscious design complying with substance-restriction requirements
- Screwed terminal connections for multi-wired (1.5-25mm²) and solid-core (1.5-35mm²) conductors
- Compact design with 1 modular spacing suitable for standard installations
Technical Specifications
| Specification |
Value |
| Product Type | Thermal Magnetic Circuit Breaker (MCB) |
| Number of Poles | 1 pole (single pole) |
| Rated Current | 6 A |
| Release Characteristic | D curve (60A-84A) |
| Rated Voltage | 230 V AC |
| Rated Insulation Voltage (Ui) | 500 V |
| Rated Impulse Withstand Voltage (Uimp) | 4 kV |
| Breaking Capacity (Icn) at 230V | 6 kA according to IEC 60898-1 |
| Breaking Capacity (Icu) at 230V | 10 kA according to IEC 60947-2 |
| Frequency Range | 50-60 Hz |
| Built-in Depth | 44 mm |
| Width | 17.8 mm (1 modular spacing) |
| Height | 94.8 mm |
| Overall Depth | 77.8 mm |
| Degree of Protection (IP) | IP20 |
| Impact Strength (IK) | IK02 |
| Operating Temperature Range | -25°C to +70°C |
| Storage Temperature Range | -40°C to +70°C |
| Connectable Conductor Cross Section (Multi-wired) | 1.5-25 mm² |
| Connectable Conductor Cross Section (Solid-core) | 1.5-35 mm² |
| Connection Type | Screwed terminal |
| Supply Direction | Top or bottom |
| Mounting Method | DIN rail |
| Pollution Degree | 2 |
| Color | Grey (RAL 7035) |
| Halogen Free | Yes |
| Explosion-proof | No |
| Flush-mounted Installation | Yes |
| Concurrently Switching Neutral | No |
| Additional Equipment Possible | Yes (DX3 auxiliaries, RCD add-on modules, accessories) |
| Reference Number | 407967 |
| EAN Code | 3245064079679 |
| Carbon Footprint (Manufacturing Phase A1-A3) | 0.946 kg CO₂ eq. |