Shop Legrand DX3 MCB 1P 1A B-Curve 6kA Circuit Breaker | 407425 In Iraq Best Prices
Single-pole thermal magnetic circuit breaker with 1A rating, B-curve characteristic, and 6kA breaking capacity. Features IP20 protection, DIN-rail mounting, and compatibility with Legrand DX3 series accessories.
The Legrand DX3 MCB (Miniature Circuit Breaker) is a thermal magnetic circuit-breaker designed to protect wiring installations against overloads and short-circuits. With a rated current of 1A and B-curve characteristic, this single-pole breaker provides a breaking capacity of 6kA at 230V, making it ideal for residential and small commercial applications. The device features IP20 protection against solid bodies larger than 12.5mm (fingerproof design) and is mounted on DIN rails for easy installation and removal. Reference number 407425 with EAN 3245064074254 ensures authentic Legrand quality and compatibility with the DX3 series ecosystem.
This circuit breaker incorporates advanced protection mechanisms with a tripping threshold for short-circuits between 3A and 5A (B-curve between 3In and 5In), providing optimal protection for sensitive circuits. The device can be supplied via copper cable, prong busbar (top or bottom side), fork busbar (bottom side), or Legrand HX3 plug busbar (top side), offering flexible installation options. With current limiting class 3 according to IEC 60898-1 standard, this MCB delivers maximum energy limitation for enhanced safety.
The DX3 MCB is equipped with two DIN rail clamps (one top, one bottom) allowing independent removal while the busbar remains in place. It features a label holder for clear circuit identification and ON/OFF indication printed on the handle with red and green backgrounds for easy status identification. Compatible with Legrand DX3 auxiliaries, RCD add-on modules, and various accessories, this breaker is halogen-free and designed with environmental consciousness. The device complies with all substance-restriction requirements and should be installed by qualified electricians in accordance with local installation rules.
Key Features
- 6kA breaking capacity at 230V according to IEC 60898-1 standard for household installations
- B-curve tripping characteristic with short-circuit threshold between 3A and 5A (3In to 5In)
- IP20 protection rating - fingerproof design protecting against solid bodies larger than 12.5mm
- Current limiting class 3 for maximum energy limitation and enhanced safety
- Flexible supply options: copper cable, prong busbar, fork busbar, or Legrand HX3 plug busbar
- Dual DIN rail clamps enabling independent removal without affecting busbar connection
- Clear circuit identification with label holder and ON/OFF status indication on handle
- Compatible with Legrand DX3 auxiliaries, RCD add-on modules, and accessories
- Halogen-free construction with environmentally conscious design process
- Aluminum cable compatible with terminal accessory n° 4 063 10
Technical Specifications
| Specification |
Value |
| Product Type | Miniature Circuit Breaker (MCB) - Thermal Magnetic |
| Manufacturer | Legrand |
| Model Series | DX3 |
| Reference Number | 407425 |
| EAN Code | 3245064074254 |
| Number of Poles | 1 pole (1P) |
| Rated Current | 1 A |
| Release Characteristic | B-curve |
| Rated Voltage | 230 V AC |
| Rated Insulation Voltage (Ui) | 500 V |
| Rated Impulse Withstand Voltage (Uimp) | 4 kV |
| Breaking Capacity (Icn) | 6 kA at 230V according to EN 60898 |
| Breaking Capacity (Icu) | 10 kA at 230V according to IEC 60947-2 |
| Short-Circuit Tripping Threshold | Between 3A and 5A (B-curve 3In to 5In) |
| Current Limiting Class | Class 3 |
| Frequency | 50-60 Hz |
| Degree of Protection (IP) | IP20 |
| Degree of Impact Strength (IK) | IK02 |
| Built-in Depth | 44 mm |
| Width | 17.8 mm |
| Height | 94.8 mm |
| Total Depth | 77.8 mm |
| Width in Modular Spacings | 1 module |
| Connectable Conductor Cross-Section (Solid-Core) | 1.5-35 mm² |
| Connectable Conductor Cross-Section (Multi-Wired) | 1.5-25 mm² |
| Connection Type | Screwed Terminal |
| Supply Direction | By top or bottom |
| Mounting Method | DIN Rail |
| Flush-Mounted Installation | Yes |
| Concurrently Switching Neutral Conductor | No |
| Pollution Degree | 2 |
| Operating Temperature Range | -25 to 70 °C |
| Storage Temperature Range | -40 to 70 °C |
| Colour | Grey |
| RAL Number | 7035 |
| Halogen Free | Yes |
| Label Space/Information Surface | Yes |
| Additional Equipment Possible | Yes |
| Explosion-Proof | No |
| Carbon Footprint (Manufacturing Phase) | 0.930 kg CO2 eq. |
| Voltage Type | AC |
Order Legrand DX3 MCB 1P 1A B-Curve 6kA Circuit Breaker | 407425 at wholesale prices for companies and factories in Iraq and Middle East, get the best deals on bulk purchases, contact us today.