| Product Type | Motor Contactor |
| Brand | Legrand |
| Model | CTX³ |
| Reference Number | 416346 |
| EAN Code | 3414970403605 |
| Rated Operation Current AC-3 at 400V | 630A |
| Rated Operation Current AC-1 at 400V | 660A |
| Rated Operation Current AC-4 at 400V | 400A |
| Rated Operation Power AC-3 at 400V | 330 kW |
| Rated Operation Power AC-4 at 400V | 200 kW |
| Number of Main Contacts | 3 Normally Open (NO), 0 Normally Closed (NC) |
| Auxiliary Contacts | 2NO + 2NC (Mirror Contact Configuration) |
| Control Supply Voltage AC 50Hz | 170-264V |
| Control Supply Voltage AC 60Hz | 170-264V |
| Control Supply Voltage DC | 170-242V |
| Voltage Type for Actuating | AC/DC |
| Main Circuit Connection Type | Screw Connection M16 |
| Wire Size Range - Power Circuit | 1.25mm² to 5.5mm² |
| Wire Size Range - Coil | 1.25mm² to 5.5mm² |
| Wire Size Range - Auxiliary Circuit | 1.25mm² to 5.5mm² |
| Mechanical Endurance | Up to 2 million operations |
| Electrical Endurance | Up to 0.5 million operations |
| Operation Cycles per Hour AC-3 | 1200 cycles |
| Suitable for Distribution Board | No |
| Installation Method | Mounting on mounting plate |
| Front Cover | Removable for visual inspection |
| Coil Design | Engineered for easy replacement |
| Compliance Standards | IEC 60947-4-1, IEC 60947-1 |
| Environmental Compliance | RoHS Directive, REACH Compliant |
| Product Carbon Footprint | 194.750 kg CO₂ eq (Manufacturing Phase A1-A3) |
| Application Areas | Tertiary and Industrial Installations |
| Recommended Uses | Inductive and non-inductive loads, motor switching |