In stock
SKU
LC1D65AM7
IQD 107,000
- [Ue] rated operational voltage : Power circuit: <= 690 V AC 25...400 Hz
- Power circuit: <= 300 V DC
About The Product
TeSys D contactor, 3 poles (3NO), for motor control applications up to 65A/440V AC-3/3e (30kW@400V). control connection by screw clamp terminals, it procures high reliability and durability.
Technical Data
- [Ue] rated operational voltage : Power circuit: <= 690 V AC 25...400 Hz
- Power circuit: <= 300 V DC
- [Ie] rated operational current : 80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
- 65 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
- 65 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
- [Uc] control circuit voltage : 220 V AC 50/60 Hz
- Motor power kW : 11 kW at 400 V AC 50/60 Hz (AC-4)
- 18.5 kW at 220...230 V AC 50/60 Hz (AC-3)
- 30 kW at 380...400 V AC 50/60 Hz (AC-3)
- 37 kW at 500 V AC 50/60 Hz (AC-3)
- 37 kW at 660...690 V AC 50/60 Hz (AC-3)
- 18.5 kW at 220...230 V AC 50/60 Hz (AC-3e)
- 30 kW at 380...400 V AC 50/60 Hz (AC-3e)
- 37 kW at 500 V AC 50/60 Hz (AC-3e)
- 37 kW at 660...690 V AC 50/60 Hz (AC-3e)
- Motor power hp : 40 hp at 460/480 V AC 50/60 Hz for 3 phases motors
- 5 hp at 115 V AC 50/60 Hz for 1 phase motors
- 10 hp at 230/240 V AC 50/60 Hz for 1 phase motors
- 20 hp at 200/208 V AC 50/60 Hz for 3 phases motors
- 20 hp at 230/240 V AC 50/60 Hz for 3 phases motors
- 50 hp at 575/600 V AC 50/60 Hz for 3 phases motors
- Pole contact composition : 3 NO
- [Ith] conventional free air thermal current : 10 A (at 60 °C) for signaling circuit
- 80 A (at 60 °C) for power circuit
- Irms rated making capacity : 140 A AC for signaling circuit conforming to IEC 60947-5-1
- 250 A DC for signaling circuit conforming to IEC 60947-5-1
- 1000 A at 440 V for power circuit conforming to IEC 60947
- Rated breaking capacity : 1000 A at 440 V for power circuit conforming to IEC 60947
- Power dissipation per pole : 9.6 W AC-1
- 6.3 W AC-3
- 6.3 W AC-3e
- Pollution degree : 3
- [Uimp] rated impulse withstand voltage : 6 kV conforming to IEC 60947
- Mechanical durability : 6 Mcycles
- Electrical durability : 1.4 Mcycles 80 A AC-1 at Ue <= 440 V
- 1.45 Mcycles 65 A AC-3 at Ue <= 440 V
- 1.45 Mcycles 65 A AC-3e at Ue <= 440 V
- Control circuit voltage limits : 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz
- 0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz
- 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz
- 1...1.1 Uc (60…70 °C):operational AC 50/60 Hz
- Inrush power in VA : 140 VA 60 Hz cos phi 0.75 (at 20 °C)
- 160 VA 50 Hz cos phi 0.75 (at 20 °C)
- Hold-in power consumption in VA : 13 VA 60 Hz cos phi 0.3 (at 20 °C)
- 15 VA 50 Hz cos phi 0.3 (at 20 °C)
- Heat dissipation : 4…5 W at 50/60 Hz
- Operating time : 4...19 ms opening
- 12...26 ms closing
- Maximum operating rate : 3600 cyc/h 60 °C
- Permissible ambient air temperature around the device : -40…60 °C
- 60…70 °C with derating
- Fire resistance : 850 °C conforming to IEC 60695-2-1
- Height : 122 mm
- Width : 55 mm
- Depth : 120 mm
- Net weight : 0.86 kg