In stock
SKU
LC1K0601M7
IQD 15,000
- [Ue] rated operational voltage : Power circuit: <= 690 V AC <= 400 Hz
- Signalling circuit: <= 690 V AC <= 400 Hz
About The Product
TeSys K contactor, 3 poles (3NO), for motor control applications up to 6A/690V AC-3 (2.2kW@400V),1NC built-in auxiliary contact, connection by screw clamp terminals. For operating rates until 600 cycles/hour and environments until 50°C, it procures reliability and durability to standard applications.
Technical Data
- [Ue] rated operational voltage : Power circuit: <= 690 V AC <= 400 Hz
- Signalling circuit: <= 690 V AC <= 400 Hz
- [Ie] rated operational current : 6 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
- 6 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
- Control circuit type : AC at 50/60 Hz
- [Uc] control circuit voltage : 220...230 V AC 50/60 Hz
- Motor power kW : 1.5 kW at 220...230 V AC 50/60 Hz AC-3
- 2.2 kW at 380...415 V AC 50/60 Hz AC-3
- 3 kW at 440/690 V AC 50/60 Hz AC-3
- 1.5 kW at 220...230 V AC 50/60 Hz AC-3e
- 2.2 kW at 380...415 V AC 50/60 Hz AC-3e
- 3 kW at 440/690 V AC 50/60 Hz AC-3e
- 1.5 kW at 220...230 V AC 50/60 Hz AC-4
- 2.2 kW at 380...415 V AC 50/60 Hz AC-4
- 3 kW at 440/690 V AC 50/60 Hz AC-4
- [Uimp] rated impulse withstand voltage : 8 kV
- [Ith] conventional free air thermal current : 20 A (at 60 °C) for power circuit
- 10 A (at 50 °C) for signaling circuit
- Irms rated making capacity : 110 A AC for power circuit conforming to IEC 60947
- 110 A AC for signalling circuit conforming to IEC 60947
- Rated breaking capacity : 110 A at 220...230 V conforming to IEC 60947
- 110 A at 380...400 V conforming to IEC 60947
- 110 A at 415 V conforming to IEC 60947
- 110 A at 440 V conforming to IEC 60947
- 80 A at 500 V conforming to IEC 60947
- 70 A at 660...690 V conforming to IEC 60947
- Inrush power in VA : 30 VA (at 20 °C)
- Hold-in power consumption in VA : 4.5 VA (at 20 °C)
- Heat dissipation : 1.3 W
- Tightening torque : 0.8…1.3 N.m - on screw clamp terminals Philips No 2
- 0.8…1.3 N.m - on screw clamp terminals flat Ø 6 mm
- 0.8…1.3 N.m - on screw clamp terminals pozidriv No 2
- Operating time : 10...20 ms coil de-energization and NO opening
- 10...20 ms coil energization and NO closing
- Mechanical durability : 10 Mcycles
- Electrical durability : 1.3 Mcycles 6 A AC-3 at Ue <= 440 V
- 1.3 Mcycles 6 A AC-3e at Ue <= 440 V
- 0.05 Mcycles 36 A AC-4 at Ue <= 440 V
- Height : 58 mm
- Width : 45 mm
- Depth : 57 mm
- Net weight : 0.18 kg